Find a Store

The Fluke T6-1000 PRO Electrical Tester lets you measure up to 1000 V AC and 200 A AC through the open fork—no direct contact with live voltage needed. Simply connect the black lead to ground with the heavy-duty alligator clip, slide the wire into the fork, and view voltage and current simultaneously. Compatible with wires up to AWG 4/0 (120 mm²) carrying 200 A and 1000 V AC, it’s easy to use even with gloves and transforms the way you work.

 
 

Technical Specifications

FunctionRangeResolutionAccuracy
FieldSense AC Voltage1000 V1 V±(3 % + 3 counts) 45 Hz – 66 Hz
FieldSense AC Current200.0 A0.1 A±(3 % + 3 counts) 45 Hz – 66 Hz
FieldSense Frequency45 Hz – 66 Hz1 Hz±(1 % + 2 counts)
Volts AC1000 V1 V±(1.5 % + 2 counts) 45 Hz – 66 Hz
Volts DC1000 V1 V±(1 % + 2 counts)
Resistance2000 Ω / 20.00 kΩ / 100.0 kΩ1 Ω / 0.01 kΩ / 0.1 kΩ±(1 % + 2 counts)
Calibration Cycle1 year
Dimensions61 mm x 259 mm x 43 mm
Weight0.35 kg (0.78 lb)
Fork Opening17.8 mm (0.7”)
Operating Temperature-10 °C to +50 °C (14 °F to 122 °F)
Storage Temperature-30 °C to +60 °C (-22 °F to +140 °F)
Operating Altitude2000 m (6,562 ft)
Storage Altitude10,000 m (32,808 ft)
Relative Humidity0% to 90% (5 °C to 30 °C)
0% to 75% (30 °C to 40 °C)
0% to 45% (40 °C to 50 °C)
Battery Type2 x AA (IEC LR6)
Battery LifeTypical 360 hrs (200 hrs using FieldSense)
Temperature Coefficient0.1 x (specified accuracy)/°C
for <18 °C or >28 °C
Safety RatingIEC 61010-1 / IEC 61010-2-032CAT IV 600 V / CAT III 1000 V
EMCIEC/EN 61326-1Portable

Key Features

  • Save time by seeing voltage and current measurements at the same time
  • Visual Continuity™ – screen turns green for continuity when it’s too loud to hear the beeper
  • FieldSense™ technology for AC voltage, current, and frequency without direct electrical contact
Write Your Own Review
You're reviewing:Fluke T6-1000 Electrical Tester
Your Rating
More Information
Specifications Description

The T6-1000 lets you take True rms voltage and current measurements quickly and safely, without the hassle of test leads. Its unique FieldSense™ technology detects the electrical field around a live conductor, enabling accurate measurements without direct contact. Featuring a HOLD button for freezing readings, large easy-to-read display with backlight, and compatibility with the Fluke TPACK ToolPak™ Magnetic Meter Hanger, this tester enhances productivity and convenience in any work environment.

How FieldSense™ technology works: FieldSense™ technology interprets the electrical field around a conductor to provide accurate voltage measurements. By interacting with a T6 reference signal, the tester displays voltage values on its screen without requiring physical contact with the conductor.

Specifications: Measurement Specifications:

  • FieldSense ac voltage true-rms: 1000 V, Resolution: 1 V, Accuracy: ± (3 % + 3 counts) 45 Hz - 66 Hz
  • FieldSense ac current true-rms: 200.0 A, Resolution: 0.1 A, Accuracy: ± (3% + 3 counts) 45 Hz - 66 Hz
  • FieldSense frequency (Hz): 45 Hz – 66 Hz, Resolution: 1 Hz, Accuracy: ± (1% + 2 counts)
  • Volts ac true-rms: 1000 V, Resolution: 1 V, Accuracy: ± (1.5% + 2 counts) 45 Hz - 66 Hz
  • Volts dc: 1000 V, Resolution: 1 V, Accuracy: ± (1% + 2 counts)
  • Resistance: 2000 Ω (Resolution: 1 Ω, Accuracy: ± (1% + 2 counts)), 20.00 kΩ (Resolution: 0.01 kΩ), 100.0 kΩ (Resolution: 0.1 kΩ)
  • Safety: 1000 V CAT III, 600 V CAT IV

General Specifications:

  • Calibration: 1-year calibration cycle
  • Dimensions: 61.1 x 259.3 x 43.8 mm
  • Jaw opening: 17.8 mm
  • Weight: 0.35 kg (0.78 lb)
  • Temperature:
    • Operating: -10 °C to +50 °C (14 °F to 122 °F)
    • Storage: -30 °C to +60 °C (-22 °F to +140 °F)
  • Altitude:
    • Operating: Up to 2,000 m (6,562 feet)
    • Storage: Up to 10,000 m (32,808 feet)
  • Relative Humidity:
    • 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
    • 0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
    • 0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
  • Battery Type and Life: 2 x AA (IEC LR6); 360 hours continuous (typical); 200 hours using FieldSense
  • Temperature coefficient: 0.1 x (specified accuracy) / °C for <18°C or >28 °C
  • Safety: IEC/EN 61010-1: Pollution Degree 2
  • Electromagnetic Environment: IEC/EN 61326-1: Portable
Package Weight (kg) 0.270000
Package Length (cm) 33.53
Package Width (cm) 13.72
Package Height (cm) 5.84